Detroit Diesel — Purge the Hydrostarter System

Maintenance · Hydrostarter hydraulic starting system

From a Detroit Diesel service manual — check it applies to your exact model before use.

Before you start

  • The oil pressure in the system must be released prior to servicing the Hydrostarter motor or other components to prevent possible injury to personnel or equipment.

Procedure

  1. Loosen the lock nut and rotate the by-pass valve on the hand pump inlet one turn counterclockwise.
  2. Operate the hand pump for 12 to 15 complete strokes; do not pump too rapidly.
  3. Close the by-pass valve tightly and tighten the lock nut.
  4. Engage the starter pinion and operate the hand pump until the starter has turned several revolutions; close the control valve.
  5. Loosen the swivel hose fitting at the engine-driven pump discharge about two turns and operate the hand pump until oil appears; tighten the fitting.
  6. Run the engine at least 1500 rpm and purge the engine-driven pump of air; tighten the fitting when oil is free of bubbles.
  7. Examine all high pressure hoses, connections and fittings for leaks.
  8. Fill the reservoir to the proper level.

Specs & values

  • Accumulator precharge pressure 1250 psi (10 413 kPa) at 70F (21C)
  • System pressure 2900 to 3300 psi (19 981 to 22 737 kPa)

Source: Detroit Diesel service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.