Detroit Diesel — Exciter Field Test Procedure

Testing & diagnosis · Exciter field winding

From a Detroit Diesel service manual — check it applies to your exact model before use.

Before you start

  • Hazardous voltage. Operate the generator set only when all guards and electrical enclosures are in place.

Procedure

  1. Place master switch to OFF/RESET.
  2. Disconnect starting battery, negative lead first.
  3. Disconnect the FP/FN leads.
  4. Check exciter field resistance with an ohmmeter across FP and FN leads.
  5. Megohmmeter test: apply 500 V DC to FP or FN lead and exciter field frame; replace if less than ~500 kOhms.

Tools required

Tool links are Amazon searches (affiliate links); manufacturer special tools may only be available from a dealer.

Specs & values

  • Good insulation reading approximately 500 kOhms (1/2 megohm) and higher

Source: Detroit Diesel service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.