Detroit Diesel — Exciter Armature Test Procedure

Testing & diagnosis

From a Detroit Diesel service manual — check it applies to your exact model before use.

Procedure

  1. Disassemble the alternator.
  2. Disconnect the armature leads from the RRA AC terminals.
  3. With ohmmeter on R x 1 scale, check resistance across exciter armature leads.
  4. Megohmmeter test: apply 500 V DC to either armature lead and armature frame; replace if less than ~500 kOhms.

Tools required

Tool links are Amazon searches (affiliate links); manufacturer special tools may only be available from a dealer.

Specs & values

  • No continuity indicates an open armature winding
  • Good insulation reading approximately 500 kOhms (1/2 megohm) and higher

Source: Detroit Diesel service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.