Before you start

  • Both utility and GenSet power must be disconnected and the GenSet disabled while maintenance is performed.

Procedure

  1. De-energize the power system and disable the operational capability of the GenSet.
  2. Dust and vacuum all controls, meters, circuit breakers and bus compartments.
  3. Wash cabinet surfaces and meter faces with a damp (mild detergent and water) sponge.
  4. Visually inspect system buswork and supports for carbon tracking, cracks, corrosion, or deterioration.
  5. Check buswork hardware, control wiring, power cables and cabinets for loose connections or missing hardware.
  6. Tighten all system buswork, control wiring, power cable, and cabinet hardware.
  7. Service or replace the GenSet batteries and verify battery charger operation.
  8. Run a Periodic Running Test and operate all controls while observing meters and indicator lights.
  9. Check the operational capability of all protective circuits and devices while observing meters and lights.

Source: Cummins/Onan service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.