Cummins/Onan — With-Load Standby System Test

Operation · Transfer panel

From a Cummins/Onan service manual — check it applies to your exact model before use.

Browse Cummins/Onan generators & specs →

Before you start

  • Close and lock the cabinet door when not working inside the cabinet.

Procedure

  1. Move the Load/No-Load switch on the control circuit board to the Load position.
  2. Keep the Auto/Man switch in the Auto position to enable automatic retransfer.
  3. Replace the cover over the circuit board and close the cabinet door.
  4. Notify occupants and turn off electronic devices prior to removing utility power.
  5. Reduce load until total does not exceed 80% of the generator kW rating.
  6. Remove the AC utility power to the transfer panel.
  7. Activate the remote test input. Generator should start and assume load after time delays.
  8. Deactivate remote test input and restore AC utility power.

Source: Cummins/Onan service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.