Cummins/Onan WC4-10S-5 — Starting the Power Unit Electrically

Operation

For the Cummins/Onan WC4-10S-5, from the Cummins/Onan service manual.

Browse Cummins/Onan generators & specs →

Before you start

  • Make no attempt to start the power unit until all preparation instructions have been complied with.

Procedure

  1. Check oil level with bayonet gauge; fill to FULL mark.
  2. Turn Automatic Voltage Regulator control rheostat to extreme counterclockwise position.
  3. See that the Two-Way Field Circuit Switch is in the Automatic position.
  4. Press START button firmly until the power unit starts, not more than 10 or 15 seconds; if it fails to start, wait 10 seconds and repeat.
  5. If it does not start after a few attempts, check fuel supply and ignition wires.
  6. Check oil pressure gauge immediately after starting; after warm-up it will be approximately 25 to 30 pounds.
  7. Turn the Automatic Voltage Regulator control rheostat slowly clockwise to increase output voltage to desired value.
  8. Allow the power unit to warm up until it operates smoothly, then connect the load.
  9. Adjust frequency with the INCREASE or DECREASE buttons of the frequency control switch.

Specs & values

  • Oil pressure approximately 25 to 30 pounds at normal operating temperature

Source: Cummins/Onan service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.