Cummins/Onan — Ventilation and Cooling Installation
Installation
From a Cummins/Onan operator's manual covering: 305CCK, 4CCK, 5CCK. Check it applies to your exact model before use.
Applies to: Cummins/Onan CCK engine
Procedure
- Pressure cooled plants require air inlet and outlet of 5 sq ft.
- Position outlet above and rear of plant; inlet opposite blower housing.
- Vacu-Flo cooling has reversed air flow; provide air inlet of at least 1 sq ft.
- Duct heated air outside.
- Use canvas section at plant to absorb vibration.
- Pitch duct upward toward outlet to minimize vapor lock.