Cummins/Onan — Undervoltage Sensor Calibration (Control Package B)

Adjustments · Electronic control voltage sensors

From a Cummins/Onan service manual covering: LT 100, LT 150, LT 200, LT 260, LT 30, LT 60. Check it applies to your exact model before use.

Applies to: Cummins/Onan TGHAA

Before you start

  • AC power within the cabinet and the rear side of the cabinet door presents a shock hazard.

Procedure

  1. Normal source: turn Normal Pickup pot fully clockwise to 100% pickup.
  2. Turn Normal calibration (Cal) pot fully counterclockwise.
  3. Turn Normal Dropout pot fully clockwise to 97% dropout.
  4. Turn on Normal source and check for nominal voltage.
  5. Slowly turn the Normal Cal potentiometer clockwise until the Normal Available lamp just turns ON.
  6. Emergency source: turn Emergency Pickup pot fully clockwise to 100% pickup.
  7. Turn Emergency Cal pot fully counterclockwise.
  8. Turn Emergency Dropout pot fully clockwise to 97% dropout.
  9. Turn on Emergency source and check for nominal voltage.
  10. Slowly turn the Emergency Cal potentiometer clockwise until the Emergency Available lamp just turns ON.
  11. Turn off both power sources. Proceed to Undervoltage Pickup and Dropout Adjustments.

Tools required

Tool links are Amazon searches (affiliate links); manufacturer special tools may only be available from a dealer.

Specs & values

  • Pickup adjustable 85% to 100% of nominal voltage
  • Dropout adjustable 75% to 98% of pickup voltage

Full service-parts list: Cummins/Onan TGHAA →