Cummins/Onan — Undervoltage Sensor Calibration

Adjustments

From a Cummins/Onan service manual — check it applies to your exact model before use.

Browse Cummins/Onan generators & specs →

Before you start

  • Rear of control accessory panel and transfer switch are energized. Do not touch due to serious shock hazard!

Procedure

  1. Open the cabinet door of the automatic transfer switch.
  2. Move the operation selector switch to STOP.
  3. Turn all the undervoltage sensor knobs to minimum voltage setting.
  4. Turn the PICK-UP VOLTAGE knob of the sensor to be calibrated to its clockwise limit.
  5. Turn the PICK-UP VOLTAGE knob very slowly counterclockwise until you hear relay K3 pick up.
  6. This reading times the multiplying factor should equal the line voltage. Check line voltage with a voltmeter, divide by the factor to see if the reading is correct.
  7. If setting is too low: turn PICK-UP VOLTAGE knob to clockwise limit, then counterclockwise to desired setting; insert small screwdriver through CALIBRATE hole and turn counterclockwise very slowly unt
  8. If setting is too high: turn PICK-UP VOLTAGE knob to clockwise limit; insert small screwdriver through CALIBRATE hole and turn to its clockwise limit; turn PICK-UP VOLTAGE knob to desired setting; tur
  9. Repeat Steps 3 through 6 for each undervoltage sensor.
  10. For more accurate calibration and calibration of the % DROP-OUT DIFFERENTIAL knob, use the Onan Multi-Tester or a variac.
  11. Remove the twist-lock disconnect plug and open the control accessory panel.
  12. Remove the transformer leads from T2-1 (COM) and T2-2 (120-V) from left side of terminal strip and connect them to output leads of a 120-volt variac.
  13. Connect a voltmeter to the output leads of the variac and connect the variac to a 120-volt AC source.
  14. Reconnect the disconnect plug, turn all undervoltage sensor knobs to minimum, and adjust the Multi-Tester or variac to give a 120-volt output.
  15. Adjust PICK-UP VOLTAGE and % DROP-OUT DIFFERENTIAL knobs to desired settings; after calibration, remove disconnect plug, reconnect wire leads, install plastic cover, close panel and reconnect disconne

Tools required

Tool links are Amazon searches (affiliate links); manufacturer special tools may only be available from a dealer.

Specs & values

  • Sensor PICK-UP VOLTAGE knob range is 90 to 140 volts for a nominal 120-volt system.
  • At 120 volts output, relay K3 should pick up at 120 volts.
  • For % DROP-OUT DIFFERENTIAL calibration, with knob at maximum, lower output to 108 volts and adjust % DROP-OUT DIFFERENTIAL knob counterclockwise until relay K3 drops out; knob should read approximately 10 percent.

Source: Cummins/Onan service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.