Cummins/Onan BT BCA 400 - 4X U / 3101 E — Isolating the Transfer Switch for Service
For the Cummins/Onan BT BCA 400 - 4X U / 3101 E.
Browse Cummins/Onan generators & specs →
Procedure
- Turn the Source Select switch to the source that will be connected to the load. If bypassing to the opposite source, the power will be momentarily interrupted.
- While holding the Source Select switch, move the bypass switch handle to the source to be connected to the load.
- Release the Source Select switch. The load is now bypassed and the automatic transfer switch may be isolated for service without load interruption.
- Turn the key operated Drawout Release switch and hold against the tension of the return spring. Turn the drawout crank handle counterclockwise to the limit of its rotation.
- Release the Drawout Release switch. The lower cabinet door may be opened to service the transfer switch as required.
Tools required
- Key operated Engine Start switch
Source: manual:962-0108 Onan BT 150 - 1000 Operators Manual (6-1983) .pdf. Figures and steps are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.