Cummins/Onan — Testing the Generator (Rotor and Stator)

Testing & diagnosis · Generator rotor and stator

From a Cummins/Onan service manual — check it applies to your exact model before use.

Applies to: Cummins/Onan Performer P224 engine

Before you start

  • Many troubleshooting procedures present hazards that can result in severe personal injury or death. Only qualified service personnel should perform service.

Procedure

  1. Test field flash voltage at brush holder terminals with engine cranking; check for 12 VDC.
  2. If not present, disconnect F1 and F2 leads and check for 12 VDC while cranking engine.
  3. Test rotor grounds between each slip ring and rotor shaft (Megger at 500 VDC or more). Reading should be 100,000 ohms or greater.
  4. Test rotor for open/shorted windings between F1 and F2 leads. Resistance should be 25.47 ohms +/- 10%.
  5. Isolate stator windings and test for opens and grounds between T1-T2, T3-T4 and Q1-Q2.
  6. Resistance values: T1-T2 0.095 ohms, T3-T4 0.095 ohms, Q1-Q2 1.185 ohms (+/- 5%).

Tools required

  • Digital ohmmeter Amazon
  • Megger or insulation resistance meter Amazon

Tool links are Amazon searches (affiliate links); manufacturer special tools may only be available from a dealer.

Specs & values

  • Rotor F1-F2: 25.47 ohms +/- 10%
  • Stator T1-T2 Amazon eBay: 0.095 ohms
  • Stator T3-T4: 0.095 ohms
  • Stator Q1-Q2: 1.185 ohms
  • Rotor/stator grounds: 100,000 ohms or greater

Source: Cummins/Onan service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.