Home›Repair guides›Cummins/Onan›Testing Reactor CMR21

Cummins/Onan — Testing Reactor CMR21

Testing & diagnosis

From a Cummins/Onan service manual — check it applies to your exact model before use.

Browse Cummins/Onan generators & specs →

Procedure

  1. Leads are marked 1, 2, 3 and 4. Wires 1-2 and 3-4 are wound on the same iron core.
  2. Measure resistance between 1-2 and 3-4.
  3. Resistance between 1-2 should be 0.38 to 0.39 ohms and between 3-4 should be 0.38 to 0.46 ohms at 77°F (25°C).
  4. Resistance between coils and from any terminal to reactor frame should be infinity.

Tools required

Tool links are Amazon searches (affiliate links); manufacturer special tools may only be available from a dealer.

Specs & values

  • 0.38 to 0.39 ohms at 77°F (25°C)
  • 0.38 to 0.46 ohms at 77°F (25°C)

Source: Cummins/Onan service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.