Cummins/Onan — Testing Main Stator Windings

Testing & diagnosis

From a Cummins/Onan service manual — check it applies to your exact model before use.

Browse Cummins/Onan generators & specs →

Before you start

  • Some generators have ground connections to the frame. Check wiring diagram.

Procedure

  1. Testing For Open or Shorted Windings: Use a Wheatstone bridge or ohmmeter having at least 0.001 ohm precision.
  2. Measure electrical resistance across each pair of stator leads. Proper resistance values are in Table 5-1. All resistances should be ±10% of value shown at 68°F (20°C).
  3. If a winding is shorted, open or grounded, replace stator assembly. Before replacing, check leads for broken wires or insulation.
  4. Testing For Grounds: Use a Megger or insulation resistance meter that applies 500 VDC or more.
  5. Disconnect all stator leads and winding taps from terminals. Measure electrical resistance between any stator lead and stator laminations. Replace stator if insulation resistance is less than 1 megohm

Tools required

  • Wheatstone bridge Amazon
  • ohmmeter with at least 0.001 ohm precision Amazon
  • Megger or insulation resistance meter Amazon

Tool links are Amazon searches (affiliate links); manufacturer special tools may only be available from a dealer.

Specs & values

  • Resistance values in Table 5-1
  • at 68°F (20°C), ±10%
  • 1 megohm

Source: Cummins/Onan service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.