Cummins/Onan — Testing Main Rotor Winding

Testing & diagnosis

From a Cummins/Onan service manual — check it applies to your exact model before use.

Browse Cummins/Onan generators & specs →

Before you start

  • Be sure to remove both rotor leads so the rotating rectifiers are isolated. Failure to do this will damage the rectifiers.

Procedure

  1. Testing For Open or Shorted Winding: Use a digital ohmmeter.
  2. Disconnect main rotor field leads which connect to rotating rectifier assemblies at F1+ and F2-.
  3. Check resistance across F1+ and F2- leads. Resistance should be within ± 10% of values at 77°F (25°C): JB 2.76 to 2.82 ohms; JCA & JCB 2.50 to 2.55 ohms. If low, shorted turns; if high, open. Replace
  4. Testing For Grounds: Use a Megger or insulation resistance meter which applies 500 VDC or more.
  5. Disconnect main rotor field leads. Connect test leads between one of the two leads and rotor shaft. Meter should read 1 megohm (1,000,000 ohms) or greater.

Tools required

  • digital ohmmeter Amazon
  • Megger or insulation resistance meter Amazon

Tool links are Amazon searches (affiliate links); manufacturer special tools may only be available from a dealer.

Specs & values

  • JB: 2.76 to 2.82 ohms at 77°F (25°C)
  • JCA & JCB: 2.50 to 2.55 ohms at 77°F (25°C)
  • 1 megohm (1,000,000 ohms) or greater

Source: Cummins/Onan service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.