Cummins/Onan — Testing Generator Rotor [B]

Testing & diagnosis

From a Cummins/Onan service manual — check it applies to your exact model before use.

Applies to: Cummins/Onan HDKA, Cummins/Onan HDKAQ, Cummins/Onan HDKAR

Procedure

  1. Isolate the rotor windings by disconnecting the two leads to the brush holder.
  2. Testing for grounds: connect test leads between each ring and the rotor shaft in turn; meter should register 100,000 ohms or greater.
  3. If less than 100,000 ohms, thoroughly dry the rotor and retest; replace a grounded rotor with a new identical part.
  4. Testing for open/shorted windings: check resistance between F1 and F2 slip rings with an ohmmeter.
  5. Rotor resistance 60 Hz is 18.2 ohms; 50 Hz is 20.7 ohms (10% at 25 C).
  6. If there is a large difference, replace the defective rotor with a new, identical part.

Tools required

  • Megger or insulation resistance meter (500 VDC or more) Amazon
  • Digital ohmmeter Amazon

Tool links are Amazon searches (affiliate links); manufacturer special tools may only be available from a dealer.

Specs & values

  • Ground: 100,000 ohms or greater
  • 60 Hz rotor 18.2 ohms
  • 50 Hz rotor 20.7 ohms

Full service-parts list: Cummins/Onan HDKA →, Cummins/Onan HDKAQ →, Cummins/Onan HDKAR →

Source: Cummins/Onan service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.