Cummins/Onan — Testing Generator Rotor

Testing & diagnosis

From a Cummins/Onan service manual — check it applies to your exact model before use.

Applies to: Cummins/Onan MDKAD, Cummins/Onan MDKAE, Cummins/Onan MDKAF

Procedure

  1. Remove rotor leads F1+ and F2- from rotating rectifier assemblies.
  2. For grounds, connect test leads between F1+ and rotor shaft, then F2- and rotor shaft. Meter should register 100,000 ohms or greater.
  3. If less than 100,000 ohms, rotor is questionable; oven dry and retest.
  4. For open or shorted windings, use digital ohmmeter to check resistance between F1 and F2 leads.
  5. For 12/15 kW genset, resistance at 77°F (25°C) is 2.35 ohms ± 10%.
  6. For 16/20 kW genset, resistance at 77°F (25°C) is 2.55 ohms ± 10%.
  7. Replace defective rotor with new identical part.

Tools required

  • Megger or insulation resistance meter Amazon
  • Digital ohmmeter Amazon

Tool links are Amazon searches (affiliate links); manufacturer special tools may only be available from a dealer.

Specs & values

  • 100,000 ohms or greater
  • 2.35 ohms ± 10% at 77°F (25°C) for 12/15 kW
  • 2.55 ohms ± 10% at 77°F (25°C) for 16/20 kW

Full service-parts list: Cummins/Onan MDKAD →, Cummins/Onan MDKAE →, Cummins/Onan MDKAF →

Source: Cummins/Onan service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.