Cummins/Onan — Testing Exciter Stator, Exciter Rotor, Main Rotor and Main Stator Windings

Testing & diagnosis · generator windings

From a Cummins/Onan service manual — check it applies to your exact model before use.

Browse Cummins/Onan generators & specs →

Procedure

  1. Measure winding resistance with a Wheatstone bridge or digital ohmmeter; replace the component if not as specified in Table 5-1.
  2. Disconnect the leads and measure insulation resistance between any lead and the laminations using a megger (600 VAC or less).
  3. Replace the component if insulation resistance is less than 1 megohm (1,000,000 ohms).
  4. On the main rotor, torque the terminals to 24 in-lbs when reassembling.

Tools required

Tool links are Amazon searches (affiliate links); manufacturer special tools may only be available from a dealer.

Specs & values

  • 1 megohm
  • 24 in-lbs (2.7 Nm)

Source: Cummins/Onan service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.