Cummins/Onan — Testing AC Load Circuit Breaker - Resistance Check

Testing & diagnosis

From a Cummins/Onan service manual covering: 4BT3.9-GC1, 4BT3.9-GC2, 6BT5.9-GC1, 6BT5.9-GC2, 6CT8.3-GS/GC1, 6CTA8.3-GS/GC1, 6CTA8.3-GS/GC2. Check it applies to your exact model before use.

Browse Cummins/Onan generators & specs →

Before you start

  • Place Run/Stop/Remote switch in Stop and disconnect battery negative cable.

Procedure

  1. Disconnect line and load wires from circuit breaker.
  2. Move breaker handle to On position.
  3. Check resistance across each pole (line to load).
  4. Resistance should be very low (near zero) and relatively equal across all poles.

Tools required

Tool links are Amazon searches (affiliate links); manufacturer special tools may only be available from a dealer.

Specs & values

  • Resistance near zero

Source: Cummins/Onan service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.