Cummins/Onan — Test With or Without Load
Operation · Transfer Switch Control Panel
From a Cummins/Onan service manual covering: GT30160EQ5KA000, GT40063XN52A000, GT40063YN52A000, GT40063ZN52A000. Check it applies to your exact model before use.
Browse Cummins/Onan generators & specs →
Procedure
- Verify that the transfer switch is set to test with or without load, as desired.
- To start a test, press and hold the Test Pushbutton for two seconds or ground the Remote Test input.
- To end the test, momentarily press the Test pushbutton or remove the ground from the Remote Test input.
Source: Cummins/Onan service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.