Cummins/Onan — Test Stator Continuity
Testing & diagnosis
From a Cummins/Onan service manual covering: 02SX1N1A, 04SX1N, 04SX1N1A, 04SX1N1B, 04SX1N2B, 04SX1N3B, 04SX1N4B, 06SX1N, 06SX1N1A, 06SX1N1B, 06SX1N2B, 06SX1N3B…. Check it applies to your exact model before use.
Browse Cummins/Onan generators & specs →
Procedure
- Disconnect generator output leads in control box. Use wiring diagrams to determine output lead coding.
- Using test lamp or ohmmeter, check each winding of stator for grounding to laminations or frame.
- Using accurate ohmmeter, test resistance of each stator winding. Compare resistances obtained.
- All windings of equal output voltage should indicate about same resistance.
- Unusually low reading indicates short; high reading indicates open circuit.
- If any windings shorted, open-circuited or grounded, replace stator assembly.
- Before replacing assembly, check leads for broken wires or insulation and replace defective lead.