Home›Repair guides›Cummins/Onan›Suction Fan Applications (Code E006)

Cummins/Onan — Suction Fan Applications (Code E006)

Installation · ventilation and cooling

From a Cummins/Onan service manual — check it applies to your exact model before use.

Applies to: Cummins/Onan HDKA, Cummins/Onan HDKAL/HDKAS engine

Procedure

  1. Provide at least 6 inches (152 mm) clearance between either end of the genset and a bulkhead or other equipment.
  2. Provide an opening of at least 200 square inches of free open area in the generator end of the compartment.
  3. If the space between the radiator and an enclosure wall is greater than 1/4 inch (6.4 mm), close it off to prevent air recirculation.
  4. Duct generator cooling and engine combustion air from outside the compartment using the factory duct kit (duct adapter box adds 2.28 inches (58 mm) to genset length).
  5. Install the coolant recovery tank in accordance with the kit instructions.

Specs & values

  • 6 inches (152 mm) minimum clearance
  • 200 square inches free open area
  • duct adapter box adds 2.28 inches (58 mm)

Full service-parts list: Cummins/Onan HDKA →

Source: Cummins/Onan service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.

More Cummins/Onan repair guides →