Cummins/Onan — Stopping at Control Panel (Manual Mode)

Operation · PCC 2100 control

From a Cummins/Onan operator's manual — check it applies to your exact model before use.

Applies to: Cummins/Onan DFGB, Cummins/Onan DFGE, Cummins/Onan VTA28 engine

Before you start

  • If possible, hot shutdown under load should be avoided to help prolong the reliability of the generator set.

Procedure

  1. Run the generator set at no load for three to five minutes before stopping.
  2. Press the Manual Run/Stop button.
  3. Genset completes its normal (Local Start) shutdown sequence.
  4. Genset stops after the cool-down at idle timer (0 to 30 minutes) has timed out.
  5. Turning the O/Manual/Auto switch to O causes an immediate engine shutdown (bypasses Cool-down At Idle).

Specs & values

  • Cool-down at idle 0 to 30 minutes

Full service-parts list: Cummins/Onan DFGB →, Cummins/Onan DFGE →

Source: Cummins/Onan operator's manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.