Cummins/Onan — Starting and Stopping
Operation · generator set
From a Cummins/Onan operator's manual — check it applies to your exact model before use.
Applies to: Cummins/Onan NHEL
Before you start
- Continuous generator set overloading can cause high operating temperatures that can damage the generator windings.
- At temperatures of 40 F (4 C) and below, disconnect all loads before attempting to start the generator set.
Procedure
- Push the start-stop switch to START at the set control or remote control; release when the set starts.
- Allow unit to warm up before connecting a load.
- Apply loads; keep the load within the nameplate rating.
- To stop, remove all loads and run three to five minutes to cool down.
- Push the start-stop switch to the STOP position.