Cummins/Onan — Setting the Exerciser Clock Exercise Start and Stop Time
Operation · Exerciser clock (Control Package B)
From a Cummins/Onan service manual covering: LT 100, LT 150, LT 200, LT 260, LT 30, LT 60. Check it applies to your exact model before use.
Applies to: Cummins/Onan TGHAA
Procedure
- Press the arrow button four times to enter programming mode; letters Pr appear in the display.
- Press the arrow button to advance to the day to be programmed; clear an existing program with plus and set together.
- Press the plus button to increment the Start time; press the set button when the Start time is reached (On Mode indicated).
- Increment with the plus button to the desired Stop time; press the set button (Off Mode indicated).
- Press the arrow button to advance to the next day; the program is copied if the next day has no existing program.
- When finished programming, press the arrow button until the clock appears in the upper left corner of the display.
Specs & values
- Example to exercise the genset one hour: Start at 7:00 PM (19:00); Stop at 8:00 PM (20:00)
Full service-parts list: Cummins/Onan TGHAA →
Source: Cummins/Onan service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.