Cummins/Onan — See the Installation Manual for important recom-
For these Cummins/Onan models: BGE/NHE, Emerald Plus Series.
Browse Cummins/Onan generators & specs →
Procedure
- 6 requires a// persons handhg LPG to be
- Close the gas shutoff valve(s) at the LPG con-
- Remove the 1/8 inch pipe plug from the regula-
- Open the LPG container shutoff valve and try
- While the genset is running, check the ma-
- If the genset will not start, jumper the fuel sole-
- If the genset is operable, check LPG supply
- Disconnect any jumpers which may have been
- Continue with the test setup for adjusting LPG
- 'T' in two hoses to the end of the hose con-
- Disconnect the hose to the carburetor and at-
- If the genset is mounted in a compartment,
- Reconnect the hose to the carburetor, discon-
- Insert this Supplement in its entirety under
- On Page 2-2 replace Figure 2-1 with Figure S-1
- On Page 7-5 replace Figure 7-3a with Figure
- Insert attached Page A-11 after Appendix A
- Do not discard Supplement 965-1060,
- Look for statement “BGE Spec F through K,
- On Page 6-14, Step 6, change“12.6 and 15.4k
Source: manual:965-0528 Onan BGE (spec F-K) NHE (spec E-K) Emerald Plus series RV Genset Service Manual (09-1994).pdf. Figures and steps are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.