Home›Repair guides›Cummins/Onan›Final Inspection and Cleanup

Cummins/Onan RSS100 / RSS200 — Final Inspection and Cleanup

Maintenance · Transfer switch

For the Cummins/Onan RSS100 / RSS200, from the Cummins/Onan service manual.

Browse Cummins/Onan generators & specs →

Before you start

  • Do not use a blower to remove debris.

Procedure

  1. Inspect all wiring to be certain that all cabled connections are correct.
  2. Verify all generator start low voltage signal connections are correct.
  3. Verify wiring does not interfere with switch operation and is not damaged.
  4. Use a vacuum cleaner to remove any dust, filings, chips, or debris from the cabinet.
  5. Check the lug torque values of the power connections.
  6. Double check power supply voltages match the voltages listed on the nameplate.
  7. Make sure all covers and barriers are installed and properly fastened.

Tools required

Tool links are Amazon searches (affiliate links); manufacturer special tools may only be available from a dealer.

Source: Cummins/Onan service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.