Procedure

  1. Stop generator set.
  2. Unplug voltage regulator from wiring harness.
  3. Connect 6-volt lantern battery to F1/F2 terminals as illustrated.
  4. Start generator set.
  5. Measure output at S1-S2 (pins 2 and 3): should be 120 VAC ± 20 VAC.
  6. Measure output at Q1-Q2 (pins 11-12): should be 160 VAC ± 20 VAC.

Tools required

Tool links are Amazon searches (affiliate links); manufacturer special tools may only be available from a dealer.

Specs & values

  • 120 VAC ± 20 VAC
  • 160 VAC ± 20 VAC

Source: Cummins/Onan service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.