Cummins/Onan RGA-IN1 — Testing Rotating Rectifiers

Testing & diagnosis

For the Cummins/Onan RGA-IN1, from the Cummins/Onan service manual.

Browse Cummins/Onan generators & specs →

Procedure

  1. Disconnect all leads from assembly to be tested.
  2. Connect ohmmeter test lead to F1+ stud and other lead to CR1, CR2 and CR3 in turn; record resistance.
  3. Connect lead to F2- stud and other lead to CR4, CR5, and CR6 in turn; record resistance.
  4. Reverse ohmmeter leads and record resistance values.
  5. All resistance readings should be high in one test and low in the other. If high or low in both, rectifier assembly is defective.
  6. Replace defective rectifier assembly with new identical part.
  7. Use 23 to 26 inch lbs (2.6 to 2.9 N.m) torque when replacing nuts.

Tools required

Tool links are Amazon searches (affiliate links); manufacturer special tools may only be available from a dealer.

Specs & values

  • 23 to 26 inch lbs (2.6 to 2.9 N.m)

Source: Cummins/Onan service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.