Cummins/Onan RGA-IN1 — Testing Generator Rotor

Testing & diagnosis

For the Cummins/Onan RGA-IN1, from the Cummins/Onan service manual.

Browse Cummins/Onan generators & specs →

Procedure

  1. For grounds: remove rotor leads F1+ and F2- from rotating rectifier assemblies.
  2. Connect test leads between F1+ and rotor shaft, then between F2- and rotor shaft. Meter should register 100,000 ohms or greater.
  3. If less than 100,000 ohms, rotor is questionable. Oven dry and retest.
  4. Replace grounded rotor with new identical part.
  5. For open or shorted windings: remove rotor leads F1+ and F2- from rotating rectifier assemblies.
  6. Using ohmmeter, check resistance between F1 and F2 leads. Resistance at 77°F (25°C) should be 2.09 ohms, ±10%. If not, replace rotor.

Tools required

  • megger or insulation resistance meter Amazon
  • digital ohmmeter Amazon

Tool links are Amazon searches (affiliate links); manufacturer special tools may only be available from a dealer.

Specs & values

  • 100,000 ohms or greater
  • 2.09 ohms ±10% at 77°F (25°C)

Source: Cummins/Onan service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.