Cummins/Onan RGA-IN1 — Testing Exciter Rotor
Testing & diagnosis
For the Cummins/Onan RGA-IN1, from the Cummins/Onan service manual.
Browse Cummins/Onan generators & specs →
Procedure
- Disconnect main rotor field leads at F1+ and F2-.
- Disconnect lead wires from diodes CR1 through CR6.
- Test between exciter lead pairs T1-T2, T2-T3 and T1-T3. Resistance at 77°F (25°C) should be 540 milliohms ± 10%.
- For grounds: apply test leads between any CR lead and rotor laminations. Reading should be 100,000 ohms or higher.
- If not, exciter rotor may require oven drying and retest. A shorted rotor must be replaced.
Tools required
Tool links are Amazon searches (affiliate links); manufacturer special tools may only be available from a dealer.
Specs & values
- 540 milliohms ± 10% at 77°F (25°C)
- 100,000 ohms or higher
Source: Cummins/Onan service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.