Home›Repair guides›Cummins/Onan›Remote Control Wiring Methods

Cummins/Onan — Remote Control Wiring Methods

Installation

From a Cummins/Onan service manual — check it applies to your exact model before use.

Applies to: Cummins/Onan HDKA, Cummins/Onan HDKAJ, Cummins/Onan HDKAK

Before you start

  • EXHAUST GAS IS DEADLY! Seal all wiring openings into the vehicle interior to keep out exhaust gas.

Procedure

  1. Remove the AC terminal access cover and remove one of the control wiring knockouts.
  2. Pull out the remote control connector plug, fit the bushing around the connector leads into the knockout slot and secure the access cover.
  3. Snap the connector plug and harness receptacle together.
  4. If the harness does not have a plug, use solder-type butt connectors and heat-shrink insulation tubing to connect to the wiring from the remote panel. Use insulated 18 AWG copper conductors.
  5. Keep control leads away from AC power leads to reduce erratic operation due to induced signals.
  6. Seal the hole where the leads enter the interior of the vehicle to keep out exhaust gas. Use silicone rubber or equivalent sealant.
  7. Use a two-pole, momentary-contact, center-return/center-off control switch with an indicator light.
  8. The total load connected to P8-F (Switched B+) should not exceed 2 amp.
  9. The total load connected to P8-B (Status Light) should not exceed 2 amp.

Specs & values

  • Remote panel wiring: insulated 18 AWG copper conductors
  • Maximum load P8-F (Switched B+): 2 amp
  • Maximum load P8-B (Status Light): 2 amp

Full service-parts list: Cummins/Onan HDKA →, Cummins/Onan HDKAJ →, Cummins/Onan HDKAK →

Source: Cummins/Onan service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.

More Cummins/Onan repair guides →