Cummins/Onan — Rectifier Testing - Method B (120-volt AC Tester)
Testing & diagnosis
From a Cummins/Onan service manual covering: 02SX1N1A, 04SX1N, 04SX1N1A, 04SX1N1B, 04SX1N2B, 04SX1N3B, 04SX1N4B, 06SX1N, 06SX1N1A, 06SX1N1B, 06SX1N2B, 06SX1N3B…. Check it applies to your exact model before use.
Browse Cummins/Onan generators & specs →
Before you start
- Avoid grounding the hot lead of a tester when checking a Magneciter component installed on a generator.
Procedure
- Make certain no component part of Magneciter is electrically grounded.
- Isolate rectifier by disconnecting one end from its point of connection.
- Connect two test leads together and observe brilliance of bulb (lead resistance only).
- Connect test leads to rectifier and observe brilliance of bulb.
- Good if bulb lights with low intensity.
- Defective if bulb lights high intensity (short) or fails to light (open); replace rectifier.
- Be sure to install rectifier in proper direction per wiring diagram.