Cummins/Onan — Reactors A and B Testing - Method E (120-volt AC Tester)
Testing & diagnosis
From a Cummins/Onan service manual covering: 02SX1N1A, 04SX1N, 04SX1N1A, 04SX1N1B, 04SX1N2B, 04SX1N3B, 04SX1N4B, 06SX1N, 06SX1N1A, 06SX1N1B, 06SX1N2B, 06SX1N3B…. Check it applies to your exact model before use.
Browse Cummins/Onan generators & specs →
Procedure
- Remove exciter from generator.
- Make certain no part of Magneciter is grounded.
- Isolate gate winding by disconnecting one lead from its point of connection.
- Isolate control winding by disconnecting both leads C1 and C2 from their points of connection.
- Connect one test lead to G1 and other to G2 and observe light bulb.
- With leads still connected to gate winding, short across leads C1 and C2 and observe bulb.
- Connect one test lead to control winding lead and other to one gate winding lead and observe bulb.
- Good if bulb dark for steps 5 and 7 but bright for step 6.
- Defective if bulb low intensity for step 5, lights for step 7, or fails step 6; replacement required.