Cummins/Onan — Producing Voltage Build-up - Method J
Operation · Magneciter
From a Cummins/Onan service manual covering: 02SX1N1A, 04SX1N, 04SX1N1A, 04SX1N1B, 04SX1N2B, 04SX1N3B, 04SX1N4B, 06SX1N, 06SX1N1A, 06SX1N1B, 06SX1N2B, 06SX1N3B…. Check it applies to your exact model before use.
Browse Cummins/Onan generators & specs →
Before you start
- Have set running but be cautious!
Procedure
- Short out gate reactor(s) to temporarily remove resistance and apply full residual voltage to alternator field.
- Refer to diagrams to locate terminal points for jumper connections.
- For 04SX and 06SX press residual reset switch in Magneciter.
- Exception for Spec A: place jumper joining G1-G2-E2.
- For 07SX, 102SX, and 2SX, jumper E2 to heat sink of rectifier No. 1.
- Remove jumper wires when AC voltage starts to build up.