Cummins/Onan — Preparing GenSet for Maintenance

Maintenance · Generator Set

From a Cummins/Onan service manual — check it applies to your exact model before use.

Browse Cummins/Onan generators & specs →

Before you start

  • Starting the GenSet while performing maintenance can result in serious injury. Prevent accidental starting by performing steps 1 and 2.

Procedure

  1. On the GenSet, operate the panel Remote/Stop/Run switch to the STOP position.
  2. Disconnect the starting battery cables (negative lead first).
  3. Depress the RESET switch at the control panel to put out alarm lamps and reset the alarm circuits.
  4. Perform GenSet maintenance following the appropriate GenSet manual.
  5. Reconnect the starting battery cables and battery charger.
  6. Operate the GenSet panel Remote/Stop/Run switch to the REMOTE position.

Source: Cummins/Onan service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.