Cummins/Onan — Overcrank Test

Testing & diagnosis · Generator set overcrank relay

From a Cummins/Onan service manual — check it applies to your exact model before use.

Browse Cummins/Onan generators & specs →

Before you start

  • Take precautions against accidental starting of the generator set including disconnecting the battery cables.

Procedure

  1. Disconnect the positive lead from the starter.
  2. Insulate lead so it cannot touch metal frame.
  3. Move the operation selector switch on the engine control to REMOTE.
  4. Move the Test/Normal/Retransfer switch to TEST. Fault or overcrank lamp should light at end of crank period.
  5. Move the Test/Normal/Retransfer switch to NORMAL.
  6. Move the generator set operation selector switch to STOP.
  7. Reconnect positive lead to starter.
  8. Move the generator set operation selector switch to REMOTE.

Specs & values

  • Crank period usually factory set at 75, +15 seconds

Source: Cummins/Onan service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.