Cummins/Onan OT UCD 280 — Start-Stop Time Delay Adjustment (Solid-State)
Adjustments · Start-Stop time delay module 7
For the Cummins/Onan OT UCD 280, from the Cummins/Onan service manual.
Browse Cummins/Onan generators & specs →
Procedure
- Open the cabinet door of automatic transfer switch.
- Move the load selector switch to WITH LOAD.
- Move test transfer switch to TEST.
- With a stopwatch or watch with a second hand, measure the time until the generator set starts cranking.
- Insert a small screwdriver through the START hole in the front panel of the start-stop time delay module; turn the START potentiometer to adjust start time delay.
- Move test transfer switch to NORMAL.
- Measure time until generator set begins to shut down.
- Turn the STOP potentiometer with the small screwdriver to adjust the stop time delay.
- Repeat until desired delay times are obtained.
- Move the load selector switch to desired position, WITHOUT LOAD or WITH LOAD.
Tools required
Tool links are Amazon searches (affiliate links); manufacturer special tools may only be available from a dealer.
Source: Cummins/Onan service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.