Before you start

  • Use extreme care when operating the transfer switch manually. High voltage on transfer switch terminals presents a serious personal injury hazard.

Procedure

  1. Move the motor disconnect switch to the DOWN, manual operation position.
  2. Pull either manual operator handle in the desired direction; down for emergency, up for normal.
  3. Automatic Transfer Switch: return the transfer switch to its preferred position.
  4. Return the motor disconnect switch to the UP, automatic operation position.

Source: Cummins/Onan service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.