Cummins/Onan OT UCD 280 — Overvoltage Sensor Settings

Adjustments · AC voltage sensor modules

For the Cummins/Onan OT UCD 280, from the Cummins/Onan service manual.

Browse Cummins/Onan generators & specs →

Before you start

  • Use settings which give load protection and yet will avoid nuisance load transfers.

Procedure

  1. Open the cabinet door.
  2. Move the operation selector switch to STOP.
  3. Turn the PICK-UP VOLTAGE knob to the desired pick-up voltage at which load is transferred from the normal power source to the generator set.
  4. Turn the DROP-OUT DIFFERENTIAL knob to the desired percent deviation below the pick-up voltage.
  5. Move the operation selector switch on the engine control to REMOTE for two-wire starting or to NORMAL for three-wire starting.
  6. Close the cabinet door.

Specs & values

  • Example: 135 volts pick-up = 113 percent of nominal voltage for a 120-volt system
  • Example: 5 percent drop-out differential from 135 volts = 7-volt differential; drop-out voltage 135 - 7 = 128 volts