Cummins/Onan OT UCD 280 — Overcrank Time Adjustment (Solid-State, Three-Wire Starting Only)

Adjustments · 2 to 3 wire converter module

For the Cummins/Onan OT UCD 280, from the Cummins/Onan service manual.

Browse Cummins/Onan generators & specs →

Procedure

  1. Remove the positive lead from the generator set's start solenoid or starter.
  2. Open cabinet door of automatic transfer switch.
  3. Move the load selector switch to WITHOUT LOAD.
  4. Move the operation selector switch to NORMAL.
  5. Move test transfer switch to TEST; overcrank lamp should light at end of crank period; measure crank time.
  6. To change the time, insert a small screwdriver through the CRANK TIME hole in the front of the 2 to 3 wire converter module and turn to adjust the cranking time.
  7. Move test transfer switch to NORMAL.
  8. Push the PUSH TO RESET button on the 2 to 3 wire converter module.
  9. Repeat until the desired cranking time is obtained.
  10. Move the load selector switch to desired position.
  11. Close and lock cabinet door.
  12. Reconnect positive lead to generator set's starter or start solenoid.

Tools required

  • Stopwatch or watch with a second hand Amazon
  • Small screwdriver Amazon

Tool links are Amazon searches (affiliate links); manufacturer special tools may only be available from a dealer.

Specs & values

  • Overcrank settings are made at the factory for approximately 75 ± 10 seconds cranking

Source: Cummins/Onan service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.