Cummins/Onan OT UCD 280 — Manual Retransfer — Two Actuator Transfer Switch (Switched Neutral)

Operation · Linear actuators and manual operator handles

For the Cummins/Onan OT UCD 280, from the Cummins/Onan service manual.

Browse Cummins/Onan generators & specs →

Before you start

  • The rapid movement of the manual operator handles may cause personal injury.

Procedure

  1. With the motor disconnect switch in the DOWN, manual position, pull the lower power pole handle up, disconnecting the load from the emergency power source.
  2. Pull the lower neutral pole handle all the way up, connecting the load neutral to the neutral of the normal power source.
  3. Push the lower power pole handle up, connecting the load to the normal power source.
  4. Being sure the transfer switch is in its preferred position, return to automatic operation by moving the motor disconnect switch to the UP position.

Source: Cummins/Onan service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.