Cummins/Onan OT-A-4060A / OT-C-10050C — With-Load Standby System Test
Operation · Transfer switch
For the Cummins/Onan OT-A-4060A / OT-C-10050C, from the Cummins/Onan service manual.
Browse Cummins/Onan generators & specs →
Before you start
- AC power within the cabinet and the rear side of the cabinet door presents a shock hazard that can cause severe personal injury or death.
Procedure
- Place the Test With/Without Load selector switch on the Power Sentry control in the With Load position.
- Close the cabinet door.
- Move the Test/Normal/Retransfer switch to Test. The generator set should start and assume the load after the transfer time delay.
- At the end of the test period, move the switch to Normal to retransfer after the retransfer time delay.
- To bypass the retransfer time delay and retransfer immediately, move the switch to Retransfer and release.
- Close and lock the cabinet door.
Source: Cummins/Onan service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.