Home›Repair guides›Cummins/Onan›Out-Of-Service Protection

Cummins/Onan N52M — Out-Of-Service Protection

Maintenance · Engine

For the Cummins/Onan N52M, from the Cummins/Onan service manual.

Browse Cummins/Onan generators & specs →

Procedure

  1. Run engine until normal operating temperature.
  2. Turn off fuel supply and run engine until it stops.
  3. Drain oil from warm engine.
  4. Refill crankcase with fresh oil; attach tag indicating viscosity used.
  5. Remove spark plugs; place rust inhibitor oil in cylinders; rotate crankshaft a few times; reinstall spark plugs.
  6. Service air cleaner.
  7. Clean governor linkage.
  8. Plug exhaust outlet and fuel inlet fittings.
  9. Wipe off entire unit; coat rustable parts with light film of oil/grease.
  10. Remove battery; store separately following standard battery storage procedures.
  11. Provide entire unit with a porous cover such as canvas. Do not use plastic.

Source: Cummins/Onan service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.