Cummins/Onan M-1600-2 — Returning Generator Set to Operation

Maintenance

For the Cummins/Onan M-1600-2, from the Cummins/Onan operator's manual.

Browse Cummins/Onan generators & specs →

Before you start

  • Initial start-up might be slow due to oil in cylinders; if it fails to start, replace the spark plugs

Procedure

  1. Perform a general inspection of the generator set
  2. Check battery electrolyte level and reconnect cables
  3. Check air filter; replace if dirty
  4. Check engine oil level
  5. Open (turn on) fuel supply
  6. Start generator set at the unit
  7. Apply 50 percent load until set runs smoothly; let run one hour
  8. Remove load, run three to five minutes to cool, then push start-stop switch to STOP

Source: Cummins/Onan operator's manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.