Home›Repair guides›Cummins/Onan›Preparing Generator Set for Storage (Out-of-Service Protection)

Cummins/Onan M-1600-2 — Preparing Generator Set for Storage (Out-of-Service Protection)

Maintenance

For the Cummins/Onan M-1600-2, from the Cummins/Onan operator's manual.

Browse Cummins/Onan generators & specs →

Before you start

  • Use this procedure if set will not be in use for more than 30 days

Procedure

  1. Run generator set at 50 percent capacity for one hour
  2. Turn off fuel supply, remove air filter, squirt defogger into carburetor intake while set runs out of fuel
  3. Reassemble air filter
  4. Shut off set, remove spark plugs, pour one tablespoon (about 30 ml) standard engine oil into spark plug holes
  5. Crank engine about 10 seconds and replace spark plugs
  6. Change oil when exhaust system has cooled
  7. Disconnect cables from starting battery

Specs & values

  • one tablespoon (about 30 ml) of standard engine oil

Source: Cummins/Onan operator's manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.

More Cummins/Onan repair guides →