Cummins/Onan — Low Battery Voltage Alarm Setting
Adjustments · Battery voltage sensor module 10
From a Cummins/Onan service manual — check it applies to your exact model before use.
Browse Cummins/Onan generators & specs →
Procedure
- Open the cabinet door of the automatic transfer switch.
- Connect a DC voltmeter to the battery terminals.
- For the alarm setting, the battery should be charged until the voltage reaches approximately 12.9 to 13.3 volts for the 12-volt lead-acid battery, 25.8 to 26.6 volts for the 24-volt lead-acid battery,
- Insert a small screwdriver into the LOW opening of battery voltage sensor module 10 for adjusting potentiometer R17. Adjust to the on-off point for the LO BAT VOLT lamp. The lamp must stay off.
- Pull out the battery charger module 6. The lamp must light when the battery terminal voltage drops to 12.6 volts for the 12-volt battery, 25.2 volts for the 24-volt battery, 12.6 volts for the 10-cell
- Insert battery charger module 6 back into its normal position. The LO BAT VOLT lamp must go out as the terminal voltage returns to values listed in Step 3.
- Disconnect the voltmeter from the battery terminals.
- Close the cabinet door.
Tools required
Tool links are Amazon searches (affiliate links); manufacturer special tools may only be available from a dealer.
Specs & values
- Low battery voltage alarm settings: 12.9 to 13.3 volts for 12-volt Amazon eBay $11.99 FridayParts $65.01 lead-acid, 25.8 to 26.6 volts for 24-volt SinoCMP $247.50 lead-acid, 13.8 to 14.5 volts for 10-cell nickel-cadmium, or 27.6 to 29.0 volts for 20-cell nickel-cadmium.
Source: Cummins/Onan service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.