Cummins/Onan — Isolating AC Output Problems

Testing & diagnosis · Generator / Voltage regulator

From a Cummins/Onan service manual — check it applies to your exact model before use.

Browse Cummins/Onan generators & specs →

Before you start

  • HAZARDOUS VOLTAGE. Touching uninsulated parts inside the generator and control box can result in severe personal injury or death.
  • These procedures involve unregulated excitation of the generator. To prevent damage due to overcurrent, make sure all loads have been disconnected.

Procedure

  1. Disconnect all loads from the generator set.
  2. Remove the side access cover and disconnect the generator field leads F1 and F2 from the voltage regulator.
  3. Prepare to connect 12 volt battery positive (+) to the F1 lead and battery negative (–) to the F2 lead and to read AC output voltage across L1-L0 and L2-L0.
  4. Recheck polarity and connect battery positive (+) to the F1 lead and start the generator.
  5. Connect battery negative (–) to the F2 lead and read AC output voltage across L1-L0 and L2-L0.
  6. The generator circuitry is probably okay if rated output voltage or higher is obtained and the voltages across L1-L0 and L2-L0 are approximately the same. (Normal excitation voltage ranges from approx
  7. If the voltages are not approximately the same, troubleshoot the main stator first. If the voltages are uniformly low, troubleshoot the exciter and field circuits first.

Tools required

Tool links are Amazon searches (affiliate links); manufacturer special tools may only be available from a dealer.

Specs & values

  • Normal excitation voltage approximately 10 VDC at no-load to approximately 40 VDC at full-load

Source: Cummins/Onan service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.