Cummins/Onan — Initial Start Setup
Operation · PCC Initial Start Setup menu
From a Cummins/Onan service manual — check it applies to your exact model before use.
Applies to: Cummins/Onan DQAD, Cummins/Onan DQAE, Cummins/Onan DQAF
Before you start
- Selecting this menu resets all operating parameters to the default values for the selected genset. All previously selected setup and adjustment settings will be lost.
Procedure
- Press RESET, MENU, and PHASE SELECT buttons simultaneously to reset and display the Initial Start Setup menu.
- Use the buttons next to the up/down symbols to toggle the standby/prime option.
- Select the correct generator set model number, frequency and power rating.
- Select the correct generator set nominal line-to-line output voltage.
- Select the DELTA or WYE option.
- Select SAVE to save changes; the MAIN MENU will then be displayed.
- Make sure the 50/60Hz selector switch on the Relay Assembly is set to the desired frequency.
Full service-parts list: Cummins/Onan DQAD →, Cummins/Onan DQAE →, Cummins/Onan DQAF →
Source: Cummins/Onan service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.