Home›Repair guides›Cummins/Onan›Idle Speed Stop Adjustment

Cummins/Onan — Idle Speed Stop Adjustment

Adjustments · governor/carburetor

From a Cummins/Onan service manual covering: 4.5 MCE, 5.0 MCE, 6.5 MCE. Check it applies to your exact model before use.

Applies to: Cummins/Onan 4.5 MCE, Cummins/Onan 5.0 MCE, Cummins/Onan 6.5 MCE, Cummins/Onan MCE engine

Procedure

  1. Start set and warm up ten minutes under 1/2 to 3/4 rated load.
  2. Disconnect load and turn governor speed adjusting screw for 50 Hz (40 Hz).
  3. Set idle speed stop screw so it does not touch throttle lever tang.
  4. Turn idle speed stop screw for 55 Hz (45 Hz).
  5. Turn governor speed adjustment nut for no-load 62-63 Hz (51.5-52.5 Hz).

Specs & values

  • No-load frequency 62-63 Amazon eBay Hz (51.5-52.5 Hz)

Full service-parts list: Cummins/Onan 4.5 MCE →, Cummins/Onan 5.0 MCE →, Cummins/Onan 6.5 MCE →

Source: Cummins/Onan service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.