Home›Repair guides›Cummins/Onan›High Battery Voltage Alarm Setting

Cummins/Onan — High Battery Voltage Alarm Setting

Adjustments · Battery voltage sensor module 10

From a Cummins/Onan service manual — check it applies to your exact model before use.

Browse Cummins/Onan generators & specs →

Procedure

  1. Open cabinet door of automatic transfer switch.
  2. Connect a DC voltmeter to the battery terminals.
  3. Pull out the battery charger module 6.
  4. Connect a separate battery charger to the battery.
  5. For the alarm setting, the battery should be charged until the voltage reaches approximately 14.5 volts for a 12-volt lead-acid battery, 29.0 volts for a 24-volt lead-acid battery, 15.5 volts for a 10
  6. Insert a small screwdriver into the HIGH opening of battery voltage sensor module 10 for adjusting potentiometer R9. Adjust to the on-off point for the HI BAT VOLT lamp. The lamp must stay lit at this
  7. Unplug or turn off the battery charger. The lamp must go out as soon as voltage drops a few tenths.
  8. Turn on battery charger. The lamp must light as voltage returns to value given in Step 5.
  9. Disconnect the battery charger and voltmeter.
  10. Insert battery charger module 6 into control panel.
  11. Close cabinet door.

Tools required

  • screwdriver Amazon
  • DC voltmeter (1/2 percent accuracy preferred) Amazon
  • battery charger Amazon

Tool links are Amazon searches (affiliate links); manufacturer special tools may only be available from a dealer.

Specs & values

Source: Cummins/Onan service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.

More Cummins/Onan repair guides →